# Modbus

Source: https://ordergroup.co/glossary/modbus/
Last updated: 2026-10-10

> Modbus RTU and TCP explained for teams integrating inverters, batteries and meters: registers, polling, pitfalls and what the software must handle.

[Energy](https://ordergroup.co/glossary/energy/)
4 min read

# Modbus

Also known as: Modbus TCP, Modbus RTU, Modbus/TCP, Modbus protocol

Definition

Modbus is an open request-response protocol for reading and writing 16-bit registers and single bits in field devices. Inverters, batteries and energy meters use it over serial lines (Modbus RTU) or Ethernet (Modbus TCP).

Cite this entry

Text
"Modbus". Order Group, Software glossary, 10 October 2026. https://ordergroup.co/glossary/modbus/
HTML
`<a href="https://ordergroup.co/glossary/modbus/">Modbus</a> - Order Group`

Reviewed by [Michał Dżaman](https://ordergroup.co/authors/michal-dzaman/), Co-founder & Head of Backend
Last reviewed 10 October 2026

## How Modbus works

Modbus is a request-response protocol published by the Modbus Organization. A client (called the master on serial lines) sends a request with a function code and an address, and the server (the slave) answers. A server never sends data on its own, so every value the software sees is the answer to a question it asked.

The data model has four tables: discrete inputs (single bits, read only), coils (single bits, read and write), input registers (16-bit words, read only) and holding registers (16-bit words, read and write). Each table is addressed from 0 to 65535, and multi-byte values travel big-endian. One request carries at most 253 bytes of protocol data, which limits a single Read Holding Registers call (function 03) to 125 registers and a Write Multiple Registers call (function 16) to 123.

Modbus RTU runs on a serial line, most often two-wire RS-485. Only one master talks on the bus at a time, slaves have addresses from 1 to 247, and address 0 is a broadcast that nobody answers. Frames are separated by a silence of at least 3.5 character times and end with a CRC. The default setting is RTU mode with even parity, and 19,200 bit/s is the required default speed. The serial specification guarantees 32 devices on one RS-485 segment without a repeater; more is possible only when the devices are documented for it.

Modbus TCP wraps the same request in a 7-byte MBAP header and sends it over TCP to port 502, giving a frame of at most 260 bytes. It has no CRC of its own and relies on TCP and Ethernet checks. A one-byte unit identifier routes the request through a gateway to a serial device behind it.

Modbus defines how to move registers, not what they mean. Which address holds active power, its scale factor, units, sign and the word order of a 32-bit value are all in the manufacturer's register map. SunSpec Alliance publishes standard information models carried over Modbus, for example model 1 (common block, mandatory first), 701 (DER AC measurement), 802 (battery) and 203 (three-phase meter). Its reference client looks for the marker "SunS" at base addresses 40000, 0 and 50000.

## What Modbus means for your software

A system that reads or controls hardware over Modbus needs the following:

- Register maps are versioned configuration per device model and firmware. A new model or firmware means a new map and a test; the application stays unchanged.
- The polling plan respects the bus. On one RS-485 line requests go one at a time, so the number of devices, requests per device and response time set the shortest possible control cycle. Contiguous registers are read in one request, up to 125.
- Values are decoded per map: scale factors, signed and unsigned types, word order of 32-bit values, and rounding to the resolution the device declares.
- Writes use the unit ID (slave ID) just as reads do. Gateways that serve several devices make this mistake expensive.
- Writes are confirmed. The software reads back the register after writing and alerts when the value differs; a fire-and-forget write path leaves the system guessing what the device does.
- A failed read is marked as failed. Publishing the last good value as fresh hides an outage from the control logic.
- Access is restricted on the network. The base protocol has no user or password field, so any client that reaches port 502 can write a holding register. Keep Modbus on a local network or behind a gateway; the Modbus Organization also publishes a separate Modbus Security Protocol specification.

Writing the specification?

Add Modbus to your requirements checklist

Collect the terms your project touches and get their system requirements in one e-mail, ready for an RFP.

Modbus RTU, Modbus TCP and common alternatives
ProtocolTransportData meaningTypical use in energy

Modbus RTUSerial line, usually RS-485, slave addresses 1-247Vendor register mapInverter, meter or battery on site, often wired to an edge deviceModbus TCPTCP/IP, port 502, unit identifier for gatewaysVendor register mapLarger inverters, battery systems, RTU-to-TCP gatewaysSunSpec ModbusModbus RTU or TCPStandard SunSpec modelsInverters, batteries and meters that implement SunSpecMQTTPublish/subscribe over TCP/IPDefined by the applicationDevice-to-cloud telemetry and commandsIEC 61850Series for power utility automation from IEC TC 57Standard data modelSubstations and utility automation

## From our projects

For [Zeronest](https://ordergroup.co/case-studies/zeronest-solar-panel-monitoring-app/) each installation gets a Bzyk D200 device wired directly into the inverter over RS-485/Modbus and reporting over LTE, independent of the manufacturer's cloud and the home Wi-Fi. The platform integrates 16 inverter brands this way. Configuration registers are checked by a daily read-write-read cycle per inverter model: the system reads the values, compares them with the target, writes them, reads them again and raises an alert when the read-back differs. Failed writes can be filtered in the admin panel.

The EMS we built for [Skyfri](https://ordergroup.co/case-studies/skyfri-solar-asset-management-platform/) includes Modbus communication modules next to battery and PV control, and the work started with communication workshops with the battery supplier in February 2024.

For Global Green's battery storage sites we designed and built the Modbus module of the EMS in 2026 and mapped the registers of battery systems from two manufacturers. Testing in July 2026 found three defects that are typical for Modbus code: failed batch reads published stale values as fresh, writes ignored the configured device ID, and the write path was fire-and-forget. All three are fixed, and rounding of read values to each channel's declared resolution is in progress.

From our projects

[Zeronest - Solar Panel Monitoring App with Automated Battery Management
How Order Group built Zeronest's solar panel monitoring app: an EMS that charges, discharges or sells power based on live prices and weather.](https://ordergroup.co/case-studies/zeronest-solar-panel-monitoring-app/)

Where to get it

- [Zeronest](https://zeronest.pl/)
Zeronest offers an energy management ecosystem for homes, businesses and energy cooperatives - devices, app and platform. We build and maintain its software.

## Related terms

- [EMS](https://ordergroup.co/glossary/ems/)

Energy management system
An energy management system (EMS) is software that reads the meters, inverters and batteries on a site and sends them setpoints, deciding when to charge, discharge, curtail or trade within grid, contract and safety limits.
- [SCADA](https://ordergroup.co/glossary/scada/)

Supervisory control and data acquisition
Supervisory control and data acquisition (SCADA) is a class of industrial control systems that collects real-time data from field devices and sensors, presents it to operators and sends control commands to equipment across a plant or network.
- [Smart meter](https://ordergroup.co/glossary/smart-meter/)

A smart meter is an electricity meter that communicates both ways with the network operator's remote reading system, recording interval data such as 15-minute load profiles and accepting commands such as a power limit or disconnection.

## Sources

1. [MODBUS Application Protocol Specification V1.1b3](https://www.modbus.org/file/secure/modbusprotocolspecification.pdf) - Modbus Organization
2. [MODBUS over Serial Line Specification and Implementation Guide V1.02](https://www.modbus.org/file/secure/modbusoverserial.pdf) - Modbus Organization
3. [MODBUS Messaging on TCP/IP Implementation Guide V1.0b](https://www.modbus.org/file/secure/messagingimplementationguide.pdf) - Modbus Organization
4. [SunSpec Model Definitions](https://github.com/sunspec/models) - SunSpec Alliance
5. [MQTT Version 5.0, OASIS Standard](https://docs.oasis-open.org/mqtt/mqtt/v5.0/mqtt-v5.0.html) - OASIS

Michał Dżaman reviewed this entry. Ask how it applies to your project.

[Ask an engineer](https://ordergroup.co/contact-us/)

## FAQ

![Michał Dżaman](https://ordergroup.co/media/images/T02DHCC1Z-USU629221-c8b7d6d66b56-512.format-webp.webp)

Michał Dżaman

Co-founder & Head of Backend

[Talk to an engineer](https://ordergroup.co/contact-us/)

### Should my devices use Modbus RTU or Modbus TCP?

Use what the device supports natively. RTU on RS-485 is common on inverters and meters and needs an edge device or gateway on site; TCP is easier to reach on a site network. The data and the register map are the same in both.

### Is Modbus secure?

The base protocol has no authentication or encryption. Security comes from network design: Modbus stays on a local segment or behind a gateway, and only the edge device talks to the hardware.

### Does SunSpec replace a device's own register map?

Only for devices that implement the SunSpec models, and only for the data those models cover. Settings and alarms outside those models still come from the vendor map.

### How many devices can share one RS-485 line?

The specification guarantees 32 devices on a segment without a repeater, and addresses go up to 247. In practice the polling time per device limits the count first, because requests go one at a time.

Building a system that depends on Modbus?

See how we build software for this domain, with case studies and the stack we use.

[See Energy Hub](https://ordergroup.co/energy-hub/)

Requirements checklist

For each term we send the definition and what it requires from your software. Free, no sales call needed.
Your checklist is empty. Use the plus next to a term to add it.